Details
 
Type: INDOORS
MODEL: MJ14 - Nº: 14-009-MJ
Current transformers Indoors Type:
CURRENT UP TO 13.2 kV.
Application Range (Amp): 5-10 á 400-800
Power until (V.A.): 30/60
Class: 0.5/10p
Security factor limit: 5/10
Intensity limit thermic : 80In
Service voltage: Until 13,2 kV.
Primary rated current: 5-10 to 300-600
Secondary rated current: 5 ó 1 A.
Type: -Single or double primary. -Single or double secondary.
Insulation: Dry-resin.
Use: INTERIOR
Frecuency: 50-60 Hz upon request.
Weight: 25Kg
OTHER CHARACTERISTICS:
-Easy to assemble and to connect.
-Can be assembled in all positions for better use of avaible space.
-All transformers accept primary double relation by series and parallel connection.
-For other values of primary current, as well as secondary uses, we suggest you contact our technical service dept.
   
  All rights reserved © MakSrl. .:. Buenos Aires - Argentina Arriba .:.