Details
 
Type: INDOORS
MODEL: MT1S - Nē: 1-026-MT
Current transformers Indoors Type:
CURRENT UP TO 3.3 kV.
Application Range (Amp): 5-10 to 400-800
Power until (V.A.): 15/30
Class: 0.5/5p
Security factor limit: 5/10
Intensity limit thermic : 80In
Service voltage: Until 3,3 kV..
Primary rated current: 5-10 to 400-800 A.
Secondary rated current: 5 ķ 1 A.
Type: -Single or double primary. -Single or double secondary.
Insulation: Dry-resin.
Use: INTERIOR
Frecuency: 50-60 Hz upon request.
Weight: 10 Kg.
OTHER CHARACTERISTICS:
-Easy to assemble and to connect.
-Can be assembled in all positions for better use of avaible space.
-All transformers accept primary double relation by series and parallel connection.
-For other values of primary current, as well as secondary uses, we suggest you contact our technical service dept.
   
  All rights reserved © MakSrl. .:. Buenos Aires - Argentina Arriba .:.